Functions
3.10 Communication over PROFIBUS/PROFINET
M200D PROFIBUS/PROFINET
70 Manual, 08/2014, A5E01577426A/RS-AA/004
Ready (automatic) Device can be activated via the BUS (e.g. PLC).
Group fault At least one fault is set.
Group warning At least one warning is present.
Group prewarning At least one pre-warning is present.
Process image error The process image of the outputs contains an illegal
bit combination, e.g. motor CW and motor CCW set
simultaneously.
Bus error Fieldbus interface threshold monitoring expired.
CPU/Master STOP PLC program is no longer processed.
Trip reset executed Trip reset accepted; that is, error/fault has been
acknowledged.
Trip reset not possible Fault could not be acknowledged since the cause of
the tripping is still pending.
Automatic mode Automatic (PLC controls)
Manual bus mode Manual mode via fieldbus (HMI controls)
Manual local mode Manual local mode:
• Manual mode via Motor Starter ES
• HMI controls
• Input controls
Connection abort in manual mode During manual mode, the relevant communication
connection was interrupted for more than 5 seconds.
Parameter assignment active Yes/No
Invalid parameter value
1)
Parameter not correct
Parameters cannot be changed in ON state
1)
Attempt to change parameters while motor is is
running not permissible.
Parameter number error
1)
Specifies the first unaccepted parameter (object
number of the parameter).
Parameters disabled CPU/master active Motor starter ignores parameters from the PLC but
informs the PLC that the parameters are in order.
No external startup parameters received No new parameters have been received from the
PLC after Power ON or restart of the motor starter.
Maximum pointer deleted
1)
Preventive diagnosis statistical data has been reset.
1)
Message bits that can be deleted with trip reset