3.6 Motor protection
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
41
3.6
Motor protection
3.6.1
Thermal motor model
Description
The approximate temperature of the motor is calculated using the measured motor currents
and device parameters "Rated operating current" and "Tripping class". This indicates
whether the motor is overloaded or functioning in the normal operating range.
Response to overload - thermal motor model
You use this device parameter to specify how the motor starter is to respond in an overload
situation:
Tripping without restart (AUTO RESET = off)
Following an overload situation, the trip command cannot be reset until the motor model
has fallen below the reset threshold and after a reset command has been issued (trip
reset).
Tripping with restart (AUTO RESET = on)
WARNING
Motor restarts automatically if AUTO RESET is on.
Can Cause Death, Serious Injury, or Property Damage
The motor starter restarts automatically after the recovery time if a start command is
present. (autoreset).
Make sure that you take appropriate measures to exclude the risk of hazardous conditions.
Warning
Note
If the value of the thermal motor model exceeds the limit of 178% for self-protection of the
motor starter, the motor starter itself generates a trip command regardless of the
parameterization "Response to overload - thermal motor model".