Diagnostics
7.2 System diagnostics
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
147
7.2
System diagnostics
System diagnostics
In the M200D PROFIBUS/PROFINET, device-specific diagnostics are recorded via assigned
PROFIBUS/PROFINET error codes.
System diagnostics indicate the existence of a channel fault. The existence of further
channel-related information is also indicated.
The stored values are extracted by the starter from the diagnostics captured in data set 92.
Since there are not sufficient uniquely defined DP/PN error codes available for the starter,
different DS 92 diagnoses must be mapped to one and the same error code (= multiple
assignment; see table).
Channel-specific diagnostics:
Single error
DP/PN
Error code
DS 92
Byte.Bit
Meaning of the error
+ F24
1)
Short-circuit 1 2.2
3.2
Temperature sensor short-circuit
Circuit breaker tripped
X
X
Overload 4 2.0
2.3
Temperature sensor overload
Thermal motor model overload
X
X
Overtemperature 5 0.3 Switching element overload X
Wire break 6 2.1 Temperature sensor wire break X
Upper limit exceeded 7 4.2 I
e
upper limit violation X
Lower limit exceeded 8 4.3 I
e
lower limit violation X
Error 9 0.4
9.2
19.2
Switching element defective
Self-test error
Switching element short-circuited
Parameter assignment error 16 8.1
8.2
Invalid parameter value (at startup only)
Parameters cannot be changed in ON state
No encoder or load voltage 17 1.0
1.1
6.7
29.1
No switching element supply voltage
No supply voltage
Electronics supply voltage too low
Mains connector removed on line side
X
X
X
X
Actuator disconnection 24 2.4
4.1
4.4
4.6
4.7
14.1
Overload tripping
Asymmetry tripping
I
e
limit value tripping
Residual current tripping
Circuit breaker tripped
Tripping due to motor blocking
Cold run tripping
External error 26 5.4
5.5
5.7
7.7
6.2
6.3
18.4-5
Input tripping
Input trip end position CW
Input trip end position CCW
Process image error
Quick stop active
Sensor supply overload
Output overloaded
X
X
X
X
X
X
X
1)
In addition to the error code, error code 24 is set.