Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
217
A.1.19.2
DS232 Read/write designation
PROFIBUS: I&M 1
The following data is saved in data set DS 232:
Byte
Length
Content
Meaning
I&M header
0 ... 9 (10 bytes) Reserved
I&M data block 1
10 ... 41 (32 bytes) TAG FUNCTION Plant identifier
Fill unused positions with blanks (0x20)
42 ... 63 (22 bytes) TAG LOCATION Location designation
Fill unused positions with blanks (0x20)
A.1.19.3
DS233 Read/write installation
PROFIBUS: I&M 2
The following data is saved in data set DS 233:
Byte
Length
Content
Meaning
I&M header
0 ... 9 (10 bytes) Reserved
I&M data block 2
10 ... 25 (16 bytes) INSTALLATION_DATE Installation date
26 ... 63 (38 bytes) Reserved
A.1.19.4
DS234 Read/write description
PROFIBUS: I&M 3
The following data is saved in data set DS 234:
Byte
Length
Content
Meaning
I&M header
0 ... 9 (10 bytes) Reserved
I&M data block 3
10 ... 63 (54 bytes) DESCRIPTOR Customer-specific additional information and
explanations
Fill unused positions with blanks (0x20)