Mounting / connection
4.1 Mounting
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
99
4.1.6
Installing the communication module
Carry out the following steps to install the communication module:
Step
Description
1 Insert the connection module onto the motor starter module.
2 Secure the communication module on the motor starter module with the 4 captive screws.
PZ 2; 2 Nm
4.1.7
Replacing the communication module
Device replacement
It is possible to replace a communication module during operation.
In so doing, the system behaves as follows:
The device is disconnected from the bus. Communication with downstream devices is not
interrupted.
Forwarding of the supply voltage is not interrupted.
In the case of M200D PROFINET, a removal interrupt is generated in the unplugged
state. When reconnected to a motor starter module, an insertion interrupt is generated.