Functions
3.10 Communication over PROFIBUS/PROFINET
M200D PROFIBUS/PROFINET
68 Manual, 08/2014, A5E01577426A/RS-AA/004
Connection monitoring
If the motor starter is controlled via the device interface (Motor Starter ES or hand-held
device), this connection is monitored. If this connection is broken, the motor shuts down with
the message "Connection abort in manual mode".
To exit this state, re-establish the connection and control again using the device interface.
Setting manual mode local for local control station at the digital inputs
You can set manual mode local as follows:
Parameterize the input n action "Motor CW" or "Motor CCW" and the input n action of
another input as "Manual mode local".
As long as the second input is active, the motor starter remains in "manual mode local"
and the motor can be controlled via the digital input "Motor CW" / "Motor CCW".
3.10.2
Commands
Commands and their meaning
Using the commands, you can instruct the motor starter to perform specific actions. You can
send the following commands to the motor starter with the Motor Starter ES configuring
software, for example:
Command
Meaning
Trip reset
Resets and acknowledges error messages
Deletes message bits, if no error message is present
No effect
Emergency start ON Activates the emergency start device function
Emergency start OFF Deactivates the emergency start device function
Automatic mode Control via PLC;
cyclic and acyclic bus channel (C1)
Manual mode
Control via PC; acyclic bus channel (C2)
Control via the device interface
Factory settings All parameters assume the factory settings again except the
communication parameters. Only possible in manual mode!
Delete maximum pointer Deletes the "preventive diagnostics" statistical data
Restart Motor starter executes restart (same effect as Power