Functions
3.10 Communication over PROFIBUS/PROFINET
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
67
Manual mode local
The motor starter can be controlled with:
Integrated manual local control (key-operated switch + keypad, order variant)
Local control station at digital inputs
(Motor CW, Motor CCW, e.g. with switch module comprising test connector set or with
external switches)
Requirement: Manual mode local set (see below).
Note
A higher-priority mode can return control priority to a lower-priority mode by command
or the input action "Manual mode". This can take place using the command "Automatic
mode" or by switching off the input action "Manual mode local".
The following message bits in diagnostics data set DS92 clearly indicate which control
source currently has control priority:
Automatic mode
Manual mode bus
Manual mode bus, PC controls
Manual mode local
Input control
HMI controls
PC controls
Connection abort in manual mode
Automatic
Manual
Control priority
Manual mode bus
Manual mode local
Connection
abort in
manual mode
Automatic
mode
Manual
mode bus
Manual
mode bus,
PC controls
Manual
mode
local
Input
control
HMI
controls
PC
controls
0 0 0 1 0 0 1 0 PC via device interface
or operator panel
0 0 0 1 0 0 0 1 None
0 0 0 1 1 0 0 0 Digital input
0 1 1 0 0 0 0 0 PC via fieldbus
0 1 0 0 0 0 0 1 None
1 0 0 0 0 0 0 0 Controller (PLC)
0 0 0 1 0 1 0 0 HMI device