Configuration / parameterization
5.1 Configuring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
123
Assigning IO device names (PROFINET IO)
Introduction
Each PROFINET IO device is assigned a unique device ID at the factory (MAC address).
Each M200D PROFINET I/O device is addressed during configuration and in the user
program on the basis of its device name.
For detailed information on addressing in PROFINET IO, refer to the PROFINET System
Description.
● The programming device must be online on PROFINET to the IO device to let you assign
a device name to the interface module.
● The I/O device is configured in HW Config and assigned an IP address.
● M200D PROFINET communication module (3RK1335-0AS01-0AA0)
1. Switch on the power supplies on the M200D PROFINET.
2. Open the "Properties" window in HW Config. Enter the device name for the I/O device
and confirm your entry with "OK".
Do not use the device name "noname".
3. In HW Config, select "PLC" > "Ethernet" > "Assign Device Name".
4. Click "Assign Name" in the "Assign Device Name" window.
The device name is saved internally in the PROFINET communication module (3RK1335-
0AS01-0AA0).
The "Assign device name" dialog box displays all I/O devices used. In this case, you should
compare the MAC address of the device with the indicated MAC address and select the
proper IO device.
Identification of the I/O devices in a plant is facilitated by a node flash test. Enable the flash
test as follows:
1. Select one of the displayed I/O devices from the "Assign Device Name" dialog box.
2. Select the flash duration.
3. Click the "Flash on" button.
Both LINK LEDs flash on the selected I/O device.