Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
198 Manual, 08/2014, A5E01577426A/RS-AA/004
DS73 logbook - Read triggering operations
0 ... 3 Unsigned 32 Operating hours - device 0 ... 4 294 967 295 1 s
4 ... 5 Unsigned 16 Object number 0 ... 32767 1
6 ... 9 Unsigned 32 Operating hours - device 0 ... 4 294 967 295 1 s
10 ... 11 Unsigned 16 Object number 0 ... 32767 1
...
...
120 ... 123 Unsigned 32 Operating hours - device 0 ... 4 294 967 295 1 s
124 ... 125 Unsigned 16 Object number 0 ... 32767 1
The data record call "Logbook" returns the operating hour of the event that has occurred and
an associated object number for each entry. This data set can accommodate 21 entries.
When all locations have been overwritten, the oldest entry is overwritten again.
The latest entry is entered at the first location of the data set. The remaining entries are
moved one entry up.
The supported object numbers and their meaning are shown in the table below:
309 Switching element overload
317 Electronics supply voltage too low
318 No switching element supply voltage
319 No supply voltage
324 Temperature sensor - overload
325 Temperature sensor wire break
326 Temperature sensor - short circuit
327 Thermal motor model overload
333 Circuit breaker tripped
334 I
e
upper limit violation
335 I
e
lower limit violation
338 Residual current tripping
341 Asymmetry tripping
348 Input tripping
354 Sensor supply overload
1496 Output 1 overloaded
1497 Output 2 overloaded