Functions
3.12 Emergency start
M200D PROFIBUS/PROFINET
74 Manual, 08/2014, A5E01577426A/RS-AA/004
Emergency start
Description
Emergency start enables restart despite an internal trip command.
Emergency start is possible if
● There is an ON command for the motor. The motor is switched on despite a pending trip
cause. At a limit trip, the motor starts in the opposite direction.
● ON command pending for the brake output. This is switched on (parameter "Brake
release delay on starting" taken into account).
Emergency start is not possible if
● An OFF command is pending
● A device error is pending
Message bit: "Self-test error", "Switching element defective"
● The self-protection function of the motor starter has responded
Message bit: "Switching element overload"
● Switched/unswitched DC24V-S/DC24V-NS supply voltage missing
Message bit: "No switching element supply voltage"
"Electronic supply voltage too low"
● The blocking protection has responded
Message bit: "Tripping due to motor blocking "
● A process image error is pending
Message bit: "Process image error"
Control options for emergency start
● Parameter "Input n action" → "Emergency start" parameterized
● Commands "Emergency start ON", "Emergency start OFF"
Emergency start active Remains pending while emergency start is active,
even if the motor and brake output are switched
off.