Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
206 Manual, 08/2014, A5E01577426A/RS-AA/004
607 0 Motor current I
max
0 ... 797 % 3.125 % All
— 1 Reserved — — —
606 2 ... 3 Last trip current 0 ... 1 000 % / [unsigned 16] 3.125 % All
602 4 ... 7 Operating hours device 0 ... 16777215 / [unsigned 32] 1 min All
1)
603 8 ... 11 Number of starts motor CW 0 ... 16777215 / [unsigned 32] 1 All
604 12 ... 15 Number of starts motor CCW 0 ... 16777215 / [unsigned 32] 1 .RS... only
605 16 ... 17 Number of overload trips 0 ... 65535 / [unsigned 16] 1 All
609 20 ... 23 Motor current I
max (rms)
0 ... 20000 A / [signed 32] 0.01 A All
608 24 ... 27 Last tripping current I
A(rms)
0 ... 20000 A / [signed 32] 0.01 A All
602 28 ... 31 Operating hours motor 0 ... 4 294 967 295 / [unsigned 32] 1 s / 1 min All
611 32 ... 35 Operating hours motor current
= 18 to 49.9% of I
emax
0 ... 4 294 967 295 / [unsigned 32] 1 s / 1 min All
1)
612 36 ... 39 Operating hours motor current
= 50 to 89.9% of I
emax
0 ... 4 294 967 295 / [unsigned 32] 1 s / 1 min All
1)
613 40 ... 43 Operating hours motor current
= 90 to 119.9 % of I
emax
0 ... 4 294 967 295 / [unsigned 32] 1 s / 1 min All
1)
614 44 ... 47 Operating hours motor current
= 120 to 1000% of I
emax
0 ... 4 294 967 295 / [unsigned 32] 1 s / 1 min All
1)
616 50 ... 51 Number of switching element
overload trips
0 ... 65535 / [unsigned 16] 1 All
618 54 ... 55 Number of short-circuit trips 0 ... 65535 / [unsigned 16] 1 All
619 56 ... 59 Number of stops with mechanical
braking
0 ... 4 294 967 295 / [unsigned 32] 1 All with BO
2)
621 64-67 Number of starts output 1 0 ... 4 294 967 295 / [unsigned 32] 1 All
622 68-71 Number of starts output 2 0 ... 4 294 967 295 / [unsigned 32] 1 All
625 80-83 Number of starts output BO 0 ... 4 294 967 295 / [unsigned 32] 1 All with BO
2)
626 84-87 Maintenance timer 0 ... 4 294 967 295 / [unsigned 32] 1 s All
1)
Special feature of operating hours
The motor starter records 2 operating hour values:
The operating hours of the motor indicate how long the switching elements and thus the motor were switched on.
The operating hours of the device (motor starter) indicate how long the power supply 24 V-NS DC of the motor starter was
switched on.
Both operating hour values are recorded in data set 95 - Read statistics. They are entered in the data field "Operating
hours" alternately at 5-second intervals. The bit "Operating hours selection" specifies which of the two operating hours
values has been transferred.
[0]: Operating hours motor
[1]: Operating hours - device.
The operating hours are recorded in the range from 0 to 16,777,215 minutes in 1-second steps.
2)
BO: Brake output