Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
126 Manual, 08/2014, A5E01577426A/RS-AA/004
5.2
Parameterize
5.2.1
Parameter dependencies in the GSD/GSDML
Note
When parameterizing with the GSD/GSDML file, values can be selected that are mutually
dependent and are not permissible in combination! The relevant parameter is reported as
"Invalid parameter value" in data set 92!
The following table shows which parameters are mutually dependent and how they must be
set:
Dependent parameters
Setting
Current limit values Lower current limit < upper current limit
Temperature sensor deactivated
CLASS OFF
With CLASS OFF: "Temperature sensor deactivated" not possible
with "Temperature sensor deactivated": "CLASS OFF" not
possible
Startup mode
Max. rated operating current I
e
(only for sDSSte, sRSSte with I
e, max
= 12 A)
with direct startup mode: I
e,max
= 9.0 A
Startup mode
Trip class CLASS
(only for sDSSte, sRSSte)
with direct startup mode: Restriction to CLASS 5 (10a), 10 and
CLASS OFF
Maintenance timer warning limits Maintenance timer warning limit 1 < maintenance timer warning
limit 2
Input n signal
Input n level
Input n action
Dependencies, see Chapter Inputs (Page 53)