Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
205
708 11 Parameters disabled
CPU/master OFF
Parameterization by parameterizing master is possible
705 13 Delete Logbook -
Triggering operations
Delete logbook with recorded fault causes.
706 14 Delete Logbook - Events Delete logbook with recorded warnings and specific actions.
717 15 Cold start - ON Enables activation of the switching contacts without main power
718 16 Cold start - OFF Switches the "cold start" function off
719 17 Delete maintenance timer Deletes the timer of the maintenance function
18 ... 255 Reserved
DS94 Read measured values
504 0 Phase current I
L1(%)
0 ... 797 % / [unsigned 8] 3.125 % All
505 1 Phase current I
L2(%)
0 ... 797 % / [unsigned 8] 3.125 % All
506 2 Phase current I
L3(%)
0 ... 797 % / [unsigned 8] 3.125 % All
501 4 ... 5 Remaining motor cooling
time
0 ... 30 min / [unsigned 16] 100 ms All
502 6.0 ... 6.6 Motor heating 0 ... 200 % / [0 ... 100] 2 % All
6.7 Asymmetry [0]: No asymmetry
[1]: asymmetry (≥ 40%)
— All
503 7 Asymmetry value 0 ... 100 % / [0 ... 100] 1 % All
508 16 Output frequency 0 ... 100 Hz / [unsigned 8] 0.5 Hz sDSSte/sRSSte
509 20 Line frequency 0 to 100 Hz 0.5 Hz sDSSte/sRSSte
513 28 ... 31 Phase current I
L1(rms)
0 ... 20 000 A / [signed 32] 0.01 A All
514 32 ... 35 Phase current I
L2(rms)
0 ... 20 000 A / [signed 32] 0.01 A All
515 36 ... 39 Phase current I
L3(rms)
0 ... 20 000 A / [signed 32] 0.01 A All
517 42 Heat sink temperature -40 ... +127 °C / [unsigned 16] 1 °C sDsste/sRSSte
12 A
520 46 ... 47 Remaining time for tripping
for thermal motor model
0 ... 6 500 s / [unsigned 16] 0.1 s sDsste/sRSSte