Functions
3.8 Short-circuit protection (circuit breaker/disconnecting means)
M200D PROFIBUS/PROFINET
64 Manual, 08/2014, A5E01577426A/RS-AA/004
3.8
Short-circuit protection (circuit breaker/disconnecting means)
Description
The motor starter is equipped with an integrated circuit breaker for short-circuit protection to
ensure that the system is safe and to protect personnel. Short-circuits between one phase
and ground (= ground fault) as well as between two phases are monitored.
Properties of the circuit breaker
The circuit breaker / disconnecting means is designed for the following functions:
Disconnecting the series-connected starter and consumer from the supply voltage
Closing lockout by means of a padlock on the rotating element
Short-circuit protection for the series-connected consumer with circuit breaker
Reset in the event of a restart
Restoration of factory settings, see Factory settings
Response to circuit breaker OFF:
You can use this parameter to determine how the motor starter is to respond to a short-
circuit or to manual switch-off of the circuit breaker:
Group fault
Group fault only after ON command
Group warning
Settings
Device parameter
Default setting
Setting range
Response to circuit
breaker OFF
Group fault
Group fault
Group fault only after ON command
Group warning
Messages and actions
Message
Action
Circuit breaker tripped Dependent on parameterization

Table of Contents