3.3.2
Load type
Here, you can specify whether the motor starter must protect a single-phase or a three-
phase load.
Asymmetry detection is deactivated in the case of a single-phase load, such as a single-
phase AC motor!
The single-phase load can be connected between any two paths of the motor starter for
all mechanically switched motor starters.
Asymmetry detection is activated for three-phase loads such as three-phase
asynchronous motors. The three phase currents are compared to one another.
Note
The load type is only relevant for mechanical motor starters. Only 3-phase load types
may be connected to electronic starters.
Note
Only one motor
must be connected to a motor starter, otherwise motor protection can no
longer be guaranteed.
Settings
Device parameter
Default setting
Setting range
Load type 3-phase
3-phase
1-phase
3.3.3
Protection against voltage failure
You use this device parameter to specify whether or not the overload message must be
retained after an electronics voltage failure:
Overload
No overload
Settings
Device parameter
Default setting
Setting range
Protection against voltage failure Yes
Yes
No