Functions
3.3 Basic functions / parameters
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
29
Here, you can specify whether the motor starter must protect a single-phase or a three-
phase load.
● Asymmetry detection is deactivated in the case of a single-phase load, such as a single-
phase AC motor!
The single-phase load can be connected between any two paths of the motor starter for
all mechanically switched motor starters.
● Asymmetry detection is activated for three-phase loads such as three-phase
asynchronous motors. The three phase currents are compared to one another.
The load type is only relevant for mechanical motor starters. Only 3-phase load types
may be connected to electronic starters.
must be connected to a motor starter, otherwise motor protection can no
longer be guaranteed.
Load type 3-phase
• 3-phase
• 1-phase
Protection against voltage failure
You use this device parameter to specify whether or not the overload message must be
retained after an electronics voltage failure:
● Overload
● No overload
Protection against voltage failure Yes
• Yes
• No