3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
63
Connector monitoring
Line side connector monitoring can be deactivated.
Response when connector removed
You use this device parameter to determine how the motor starter is to behave when the
connector is unplugged:
Group fault
Group fault only after ON command
Group warning
Settings
Device parameter
Default setting
Setting range
Connector monitoring Deactivated
Deactivated
Line side
Response when
connector removed
Group fault
Group fault
Group fault only after ON command
Group warning
Messages and actions
Message
Action
Connector monitoring deactivated No monitoring on plugged-in connector
Connector disconnected on line side Dependent on parameterization
3.7.5.2
Motor connector
The "connector monitoring" function is only valid for the infeed connector.
A connector monitoring function for the motor connector can be logically combined with the
thermistor cable and/or thermistor evaluation function.
If a motor is operated without a thermistor, you can activate thermistor monitoring
(thermoclick) and use it to monitor the connector by means of a wire jumper on the motor
terminal board or in the motor connector.
Note
In this case, the "temperature sensor overload" message must be interpreted as a removed
motor connector.