Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
63
Line side connector monitoring can be deactivated.
Response when connector removed
You use this device parameter to determine how the motor starter is to behave when the
connector is unplugged:
● Group fault
● Group fault only after ON command
● Group warning
Connector monitoring Deactivated
• Deactivated
• Line side
Response when
connector removed
Group fault
• Group fault
• Group fault only after ON command
• Group warning
Connector monitoring deactivated No monitoring on plugged-in connector
Connector disconnected on line side Dependent on parameterization
The "connector monitoring" function is only valid for the infeed connector.
A connector monitoring function for the motor connector can be logically combined with the
thermistor cable and/or thermistor evaluation function.
If a motor is operated without a thermistor, you can activate thermistor monitoring
(thermoclick) and use it to monitor the connector by means of a wire jumper on the motor
terminal board or in the motor connector.
In this case, the "temperature sensor overload" message must be interpreted as a removed
motor connector.