Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
128 Manual, 08/2014, A5E01577426A/RS-AA/004
Current limit value
(x 3.125%)
• 600% (Ie ≤ 9 A)
• 550% (Ie ≤ 9 A)
• Ie ≤ 9 A: 125 % ... 600 %
• Ie > 9 A: 125 % ... 550 %
Increment: 3.125 %
Brake release delay on
starting
0 s - 2.5 to + 2.5 s
Increment: 0.01 s
Brake holding time on
stopping
0 s 0 to 25 s
Increment: 0.01 s
Motor protection (Page 41)
Response to overload -
thermal motor model
Tripping without restart
• Tripping without restart
• Tripping with restart
• Warning
Trip class
(DSte / RSte, sDSSTe,
sRSSte in startup
mode ≠ direct)
CLASS 10
• CLASS 5 (10a),
• CLASS 10
• CLASS 15,
• CLASS 20
• CLASS OFF
Trip class
(sDSSte / sRSSte in
startup mode = direct)
• CLASS 10
in startup mode = direct
• CLASS 5 (10a)
in startup mode ≠ direct
• CLASS 5 (10a),
• CLASS 10
• CLASS OFF
Recovery time 90 s 60 to 1800 s
Increment: 30 s
Prewarning limit motor
heating
0% (= deactivated) 0 ... 95 %
Increment: 5 %
Prewarning limit -
remaining time for
tripping
0 s (= deactivated) 0 to 500 s
Increment: 1 s
Idle time 0 s (= deactivated) 0 to 255 s increment: 1 s
Response to overload
temperature sensor
Tripping without restart
• Tripping without restart
• Tripping with restart
• Warning
Temperature sensor Deactivated
• Deactivated
• Themoclick
• PTC type A
Temperature sensor
monitoring
Yes
• Yes
• No
Response to residual
current detection
Trip
• Warning
• Trip