Configuration / parameterization
5.2 Parameterize
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
129
Device parameter
Default setting
Setting range
System monitoring (Page 48)
Response to current
limit violation
Warning
Warning
Trip
Lower current limit 18,75 %
18.75 to 100% of I
e
0% (= deactivated)
Increment: 3,125 %
Upper current limit 112,5 %
50 to 400% of I
e
0% (= deactivated)
Increment: 3,125 %
Blocking current 800 %
150 to 1000% von Ie
150 ... 800% of Ie
(sDS..., sRS...)
Increment: 50 %
Blocking time 1 s 1 to 5 s
Increment: 0.5 s
Response to
asymmetry
Trip
Warning
Trip
Asymmetry limit 30 % 30 ... 60% (0 = deactivated)
Increment: 10 %
Input signal extension 0 ms 0 to 200 ms
Increment: 10 ms
Input signal delay 10 ms 10 ... 80 ms
Increment: 10 ms
Input 1 level Normally open
Normally closed
Normally open
Input 2 level
Input 3 level
Input 4 level
Input 1 action No action
No action
Trip without restart
Trip with restart
Trip end position CW
Trip end position CCW
(RSte/sRSSte only)
Group warning
Manual operation local
Emergency start
Motor CW
Motor CCW (RSte/sRSSte only)
Quick stop
Trip reset
Cold run
Input 2 action
Input 3 action
Input 4 action