Diagnostics
7.1 Diagnostics with LED
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
141
DEVICE LED (possible colors: red / green / yellow / OFF)
Status
Meaning
Possible cause
Off Device not ready System error:
No electronics supply voltage (DC24V-NS)
or supply is < 18 V
Start-up parameters missing
Green Device OK
Flashing green Device not starting No start-up parameters received
Green flashing
(0.25 s on / 1.75 s off)
Energy-saving mode
active
Yellow Internal trip
Flashing yellow Group warning Group warning due to:
Thermal motor model overload
1)
Temperature sensor overload
1)
Asymmetry detected
1)
Current limit violation
1)
Connector monitoring
1)
Circuit breaker tripped/switched off
1)
Group warning via input action
Maintenance timer limit violation
Red Device defective
Flashing red Firmware updates
Self-test Motor current flowing
Flickering red Self-test No current flow
Factory settings
1)
Depends on the parameter assignment
BF/RUN LED (possible colors: red / green / OFF)
Status
Meaning
Possible cause
Off Device not in data
exchange or CPU / master
in Stop
e.g. motor starter module disconnected
Green Device in data exchange
Red Bus error Fieldbus interface unclear
Flashing red Parameterization error
Configuration error
Incorrect or invalid parameters received