Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
190 Manual, 08/2014, A5E01577426A/RS-AA/004
Statistical data maximum pointers
Maximum pointers are used for preventive diagnostics:
The maximum measured value is stored in the device.
The higher-level PLC can fetch the measured value at any time.
The higher-level PLC can delete the measured value at any time.
The following data is available in the form of a maximum pointer:
Number of motor overload trips
Operating hours - motor current = 18 to 49.9 % of I
e
Operating hours - motor current = 50 to 89.9 % of I
e
Operating hours - motor current = 90 to 119.9 % of I
e
Operating hours - motor current = 120 to 1000 % of I
e
Maximum tripping current I
A
max
(%)
Maximum tripping current I
A
max
(rms)
Phase current I
L1
max
to I
L3
max
. Maximum phase current as a percentage [%] of the current
setting I
e
and in amperes [A]
Data format: 1 byte each, 8-bit current format.
The measured maximum phase current in each case is stored per phase.
Maximum heat sink temperature (only on sDSSte/sRSSte 12 A)