Diagnostics
7.4 Diagnostics with STEP 7 on PROFIBUS DP
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
159
Fault types
The diagnostics message is signaled on channel 0.
Fault type
Error text
Meaning / cause
Delete/acknowledge message bit
1
dec
00001
B
Short-circuit
Temperature sensor - short circuit
Circuit breaker tripped
Message bit is automatically deleted when
the cause of the fault has been removed
and acknowledged with "trip reset"
4
dec
00100
B
Overload
Temperature sensor - overload
Thermal motor model - overload
Message bit is updated continually
5
dec
00101
B
Overtemperature
Overload power semiconductor
Switching element overload
Message bit is automatically deleted when
the cause of the fault has been removed
and acknowledged with "trip reset"
6
dec
00110
B
Wire break
Temperature sensor wire break
Message bit is updated continually
7
dec
00111
B
Upper limit
exceeded
I
e
upper limit violation
8
dec
01000
B
Lower limit
undershot
I
e
lower limit violation
9
dec
01001
B
Error
Internal error/device error
Self-test error
Switching element defective
Switching element short-circuited
Message bit can be deleted when the cause
of the fault has been removed by
Switching the supply voltage
(DC24 V-NS) on/off
"Restart" command if possible
16
dec
10000
B
Parameter
assignment error
Invalid parameter value
Parameters cannot be changed in
ON state
Message bit is always deleted when
acknowledged with "trip reset"
17
dec
10001
B
No encoder or
load voltage
Electronics supply voltage too low
(< 18 V)
No contact block supply voltage
No supply voltage
Connector disconnected on line
side
Message bit is deleted when the cause of
the trip has been removed or automatically
acknowledged.
24
dec
11000
B
Actuator
disconnection
Overload tripping
Residual current tripping
Asymmetry tripping
Circuit breaker tripped
I
e
limit tripping
Cold start tripping
Tripping due to motor blocking
Message bit is always deleted when
acknowledged with "trip reset".
Additional acknowledgment in combination
with another fault
26
dec
11010
B
External error
Input tripping
Input tripping - end position
(CW / CCW)
Quick stop active
Sensor supply overload
Process image error
Output overloaded
Message bit is always deleted when
acknowledged with "trip reset".