Technical data
8.2 Motor starters
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
171
Motor ratings according to UL / CSA
3RK13.5- .K (2 A)
power (3ph /hp) / max. FLA
At 460/480 V AC 0.75 hp / 1.6 A 0.75 hp / 1.6 A
At 575/600 V AC 1 hp / 1.7 A —
3RK13.5- .L (12 A)
power (3ph /hp) / max. FLA
At 230/240 V AC 3 hp / 9.6 A 3 hp / 9.6 A
At 460/480 V AC 7.5 hp / 11 A 7.5 hp / 11
At 575/600 V AC 10 hp / 11 A —
Typical switching times incl. internal
signal processing
at 0.85 to 1.1 x U
e
Closing delay
Opening delay
50 to 85 ms
40 to 65 ms
25 / 105 ms
35 / 35 ms
Mechanical service life of contactor 10 million —
Electrical service life of contactor Electrical service life of
contactor (Page 183)
—
B10 value 1000000
1)
—
Permissible switching frequency Electrical service life of
contactor (Page 183)
Switching frequency
(Page 175)
Rated surge capacity U
imp
6 kV
Rated insulation voltage U
i
500 V
Safe isolation between main and control circuits
to IEC 60947-1 Appendix N
400 V
Instantaneous overcurrent release
I
e max
= 2 A
I
e
max
= 9 / 12 A
26 A
208 A
Rated short-circuit¬breaking capacity I
CU
at 400 V in accordance with
IEC 60947
At 400 V
At 500 V
50 kA
50 kA
50 kA
20 kA
Short circuit ratings according to UL / CSA
65 kA / 480 V /
Any circuit breaker or
any fuse
10 kA / 600 V /
Any circuit breaker or
any fuse
5 kA / 480 V /
fuse: 60 A class J
42 kA / 480 V /
fuse: 45 A class J
Group installation Suitable for Group installation
Motor disconnect Suitable as motor disconnect
1) This specification refers exclusively to the mechanical switching element under its reference conditions.