Technical data
8.7 Switching frequency
M200D PROFIBUS/PROFINET
176 Manual, 08/2014, A5E01577426A/RS-AA/004
The following tables provide an overview of the switching cycles/hour according to
influencing factors.
Direct and reversing starters, electronic (sDSSte / sRSSte) up to 5.5 kW
Switching frequencies with active soft start function
Switching cycles/hour for 3RK1395-6KS71-.AD. (0.15 A to 2 A)
Installation position
Vertical
Horizontal
Rated current I
e
2 A
2 A
2 A
2 A
2 A
2 A
Ambient temperature
40 °C
50 °C
55 °C
40 °C
50 °C
55 °C
Motor protection
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
Class 5 (10a)
ED=30 %, Start 4 x I
e
/ 1 s 250 910 250 910 250 910 250 910 250 910 250 910
ED=70 %, Start 4 x I
e
/ 1 s 150 460 150 460 150 460 150 460 150 460 150 460
ED=30 %, Start 4 x I
e
/ 2 s 120 420 120 420 120 420 120 420 120 420 120 420
ED=70 %, Start 4 x I
e
/ 2 s 70 210 70 210 70 210 70 210 70 210 70 210
Class 10
ED=30 %, Start 4 x I
e
/ 2 s 120 450 120 450 120 450 120 450 120 450 120 450
ED=70 %, Start 4 x I
e
/ 2 s 70 230 70 230 70 230 70 230 70 230 70 230
ED=30%, Start 4 x I
e
/ 4 s 60 210 60 210 60 210 60 210 60 210 60 210
ED=70%, Start 4 x I
e
/ 4 s 37 100 37 100 37 100 37 100 37 100 37 100
Class 15
ED=30%, Start 4 x I
e
/ 3 s 80 300 120 450 120 450 120 450 120 450 120 450
ED=70%, Start 4 x I
e
/ 3 s 50 150 70 230 70 230 70 230 70 230 70 230
ED=30%, Start 4 x I
e
/ 6 s 40 140 60 210 60 210 60 210 60 210 60 210
ED=70%, Start 4 x I
e
/ 6 s 25 70 37 100 37 100 37 100 37 100 37 100
Class 20
ED=30%, Start 4 x I
e
/ 4 s 60 220 60 220 60 220 60 220 60 220 60 220
ED=70%, Start 4 x I
e
/ 4 s 37 110 37 110 37 110 37 110 37 110 37 110
ED=30%, Start 4 x I
e
/ 8 s 30 100 30 100 30 100 30 100 30 100 30 100
ED=70%, Start 4 x I
e
/ 8 s 18 50 18 50 18 50 18 50 18 50 18 50
1)
Duty cycle current rms value =1.15 x I
e
→ motor protection
2)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.