Technical data
8.7 Switching frequency
M200D PROFIBUS/PROFINET
182 Manual, 08/2014, A5E01577426A/RS-AA/004
Switching cycles/hour for 3RK1395-6LS71-.AD.(1.5 A to 12 A)
e
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
ED=30% (8 x I
e
) / 0.1 s 600 3400 600 2500 600 2000 600 2800 600 2100 600 2100
ED=70% (8 x I
e
) / 0.1 s 380 2000 380 1250 380 880 380 1600 380 900 380 900
ED=30% (8 x I
e
) / 0.25 s 240 1300 240 1000 240 800 240 1150 240 840 240 840
ED=70 % (8 x I
e
) / 0.25 s 150 800 150 500 150 350 150 650 150 380 150 380
ED=30% (8 x I
e
) / 0.5 s 120 700 120 500 120 400 120 580 120 430 120 430
ED=70 % (8 x I
e
) / 0.5 s 70 380 70 270 70 200 70 340 70 200 70 200
ED=30% (8 x I
e
) / 0.25 s 240 1300 240 1000 240 820 240 1100 240 820 240 820
ED=70% (8 x I
e
) / 0.25 s 160 760 160 500 160 350 160 640 160 350 160 350
ED=30 % (8 x I
e
) / 0.5 s 120 700 120 520 120 420 120 580 120 430 120 430
ED=70 % (8 x I
e
) / 0.5 s 70 400 70 280 70 200 70 340 70 200 70 200
ED=30 % (8 x I
e
) / 1 s 60 350 60 260 60 220 60 290 60 220 60 220
ED=70 % (8 x I
e
) / 1 s 37 190 37 140 37 100 37 170 37 100 37 100
1)
Duty cycle current rms value = 1.15 x I
e
→ motor protection
2)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.
Switching cycles/hour for 3RK1395-6LS71-.AD.(1.5 A to 12 A)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
ED=30 % (8 x I
e
) / 0.3 s 200 630 200 670 200 740 200 700 200 700 200 700
ED=70 % (8 x I
e
) / 0.3 s 120 280 120 290 120 330 120 320 120 320 120 320
ED=30 % (8 x I
e
) / 0.6 s 100 320 100 330 100 370 100 350 100 350 100 350
ED=70 % (8 x I
e
) / 0.6 s 60 140 60 140 60 160 60 160 60 160 60 160
ED=30 % (8 x I
e
) / 0.6 s 100 320 100 330 100 370 100 350 100 350 100 350
ED=70 % (8 x I
e
) / 0.6 s 60 140 60 140 60 160 60 160 60 160 60 160
ED=30 % (8 x I
e
) / 1.2 s 50 160 50 170 50 190 50 170 50 170 50 170
ED=70 % (8 x I
e
) / 1.2 s 30 70 30 70 30 80 30 80 30 80 30 80
1)
Duty cycle current rms value = 1.15 x I
e
→ motor protection
2)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.