Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
192 Manual, 08/2014, A5E01577426A/RS-AA/004
The following error codes are generated by the motor starter:
00
H
00
H
No error —
80
H
A0
H
Negative acknowledgment in the case of
"Read data set"
Data set write-only
80
H
A1
H
Negative acknowledgment in the case of
"Write data set"
Data set read-only
80
H
A2
H
Protocol error
• Layer 2 (fieldbus)
• Device interface
• Incorrect coordination
80
H
A9
H
This function is not supported DPV1 service does not support
Read/write data set
80
H
B0
H
Unknown data set number (DS No) DS No. not known in motor starter
80
H
B1
H
Incorrect data set length when writing DS length and specified DS length
different
80
H
B2
H
Incorrect slot number Slot not 1 or 4
80
H
B6
H
Communication partner has rejected data
transfer
• Incorrect operating mode
(automatic, manual bus, manual
local)
• Data set is read-only
• Parameters cannot be changed
in ON state
80
H
B8
H
Invalid parameter Invalid parameter value
80
H
C2
H
Temporary lack of resources in the device
• No free receive buffer
• The data set is currently being
updated
• The dataset request is currently
active on another interface.