EasyManua.ls Logo

Siemens SIRIUS M200D - Page 192

Siemens SIRIUS M200D
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.1 Data formats and data sets
M200D PROFIBUS/PROFINET
192 Manual, 08/2014, A5E01577426A/RS-AA/004
Error codes
The following error codes are generated by the motor starter:
Error codes byte
Error messages
Cause
high
Low
00
H
00
H
No error
Communication interface
80
H
A0
H
Negative acknowledgment in the case of
"Read data set"
Data set write-only
80
H
A1
H
Negative acknowledgment in the case of
"Write data set"
Data set read-only
80
H
A2
H
Protocol error
Layer 2 (fieldbus)
Device interface
Incorrect coordination
80
H
A9
H
This function is not supported DPV1 service does not support
Read/write data set
Access to technology
80
H
B0
H
Unknown data set number (DS No) DS No. not known in motor starter
80
H
B1
H
Incorrect data set length when writing DS length and specified DS length
different
80
H
B2
H
Incorrect slot number Slot not 1 or 4
80
H
B6
H
Communication partner has rejected data
transfer
Incorrect operating mode
(automatic, manual bus, manual
local)
Data set is read-only
Parameters cannot be changed
in ON state
80
H
B8
H
Invalid parameter Invalid parameter value
Device resources
80
H
C2
H
Temporary lack of resources in the device
No free receive buffer
The data set is currently being
updated
The dataset request is currently
active on another interface.

Table of Contents