Functions
3.5 Motor control
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
37
Current limit value
With the startup modes "Current limiting" and "Voltage ramp + current limiting", the motor
current is limited to a maximum value during starting.
Note
At a rated operating current ≥ 9 A, the motor starter automatically reduces the current limit
value to 550%.
Settings
Device parameter
Default setting
Setting range
Start time 5 s 0 to 30 s
Increment: 0.25 s
Run-down time 0 0 to 30 s
Increment: 0.25 s
Startup mode direct
direct
Voltage ramp
Current limiting
Voltage ramp + current limiting
Run-down type Run-down without load
Run-down without load
Voltage ramp
Starting voltage 40 % 20 % ... 100 %
Increment: 5 %
Stopping voltage 40 % 20 % ... 90 %
Increment: 5 %
Current limit value
600% (I
e
9 A)
550% (I
e
> 9 A)
I
e
9 A: 125 % ... 600 %
I
e
> 9 A: 125 % ... 550 %
Increment: 3,125 %
Messages and actions
Message
Action
Starting active The motor is switched on depending on the "Startup mode"
parameter.
Run-down active The motor is switched on depending on the "Run-down mode"
parameter.
No supply voltage ON command generates faults.
Current limiting active Motor starting current is limited.