Functions
3.7 System monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
55
Input n action
Different actions can be triggered when an input signal is present. You can parameterze the
following actions dependent on "Input n level", "Input n signal" and "Mode".
Note
If "Input n signal" = retentive and "Input n action" = Motor CW/CCW, at least one input must
always be parameterized with input action "Tripping ... " or "Quick Stop".
If this rule is violated, the motor starter will reject the parameters with the relevant
diagnostics message!
Input n action
Level
Signal
Mode
Description
No action NO/NC n-ret./ret. All -
Trip without restart NO/NC n.ret./- All
Causes the motor and brake to trip.
Must be acknowledged once the cause of the tripping
has been rectified (initial status).
Trip with restart (auto
reset)
NO/NC n.ret./- All
Causes the motor and brake to trip.
Acknowledged automatically once the cause of the
tripping has been rectified (initial status).
Trip end position CW NO/NC n.ret./- All
The motor and the brake output are tripped
regardless of the direction of rotation.
The brake output can be switched on again once the
"Brake" and "Motor CW / CCW" control commands
have been canceled.
Trip end position CW rotation: The motor can only be
switched on again with the opposite command
("Motor CCW").
Trip end position CCW The motor can only be
switched on again with the opposite command
("Motor CW").
Trip end position CCW
(RSte/sRSSte only)
NO/NC n.ret./- All
Group warning NO/NC n-ret./ret. All
The "Group warning" message is set.
The motor starter and the brake output are not
tripped!
ret.:
The input action responds to the active edge of the
input signal. Deactivation with a pending active input
signal is thus possible.
Action is deactivated with trip reset.
Manual mode local NO/NC n.ret./- All
Control is only possible via "input n action": "Motor
CW" and "Motor CCW" (see below) possible!
Control is not possible over the fieldbus ("Automatic"
mode)!
"Automatic" mode is only possible again if manual
mode local is canceled and "Input n action": "Motor
CW" or "Motor CCW" is not active.