The self-test comprises 3 test steps. The test steps are followed in dependence of the signal
duration of the test command:
1 < 2 s LED test All LEDs are switched on for 2 seconds!
• User check, no message bit
2 2 to 5 s Hardware test The hardware of the motor starter is tested;
Current measurement indicated by the "DEVICE" LED:
• Current flowing: flashing red
• Current not flowing: flickering red
• User check, no message bit
3
1)
> 5 s Trip Switching elements are switched off.
1)
This test step is only executed in manual mode
If an error occurs, the "DEVICE" LED lights up red. The error can only be acknowledged by
switching the device off and then on again. If the error is still present, the self-test will return
an error again when the device is switched on. In this case, the motor starter must be
replaced.
Self-test active -
Self-test ok -
Self-test error -
Specific device components are monitored continuously (internally) by the motor starter and
the results signaled with the self-test messages. The message "Self-test error" can also
appear in the case of an internal monitoring fault without the self-test having been activated.