General Operation
7.7 Pump Control
SITRANS LUT400
110 Operating Instructions, 07/2019, A5E33329501-AC
The SITRANS LUT400 will not sacrifice other pumping strategies to ensure that the
service ratio is held true.
If the pump ratios are set to the same value, then the ratio equals 1:1 and all pumps are
used equally (default).
When a pump start is required (ON Setpoint), the pump with the fewest running hours (with
respect to the assigned ratio values) starts.
Conversely, when a pump stop is required (OFF Setpoint), if multiple pumps are running
simultaneously, the pump with the most running hours (as compared to the assigned ratio
values) stops.
7.7.4 Setting a pump up (reservoir) group
Sets a group of two pumps to pump up a reservoir.
* ON Setpoint Pump 1 / Pump 2
** OFF Setpoint Pump 1 / Pump 2