General Operation
7.7 Pump Control
SITRANS LUT400
106 Operating Instructions, 07/2019, A5E33329501-AC
7.7.2.4 Set the OFF Setpoints
Parameter
Sample Value
1
Description
OFF Setpoint Pump 1
(2.7.1.7.) (Page 186)
0.5 m** Sets the level at which pump 1 turns off. The first
cycle will use this setpoint. Subsequent cycles
rotate the setpoint among the pumps. For exam-
ple: In cycle 1, pump 1 turns off at 0.5 m. In the
next cycle, pump 2 will turn off at 0.5 m.
OFF Setpoint Pump 2
(2.7.1.9.) (Page 186)
0.6 m** Sets the level at which pump 2 turns off.
1)
Sample values denoted by asterisks in illustration on Setting a pump down (wet well) group
(Page 104).
7.7.3 Other Pump Control algorithms
7.7.3.1 Set Relays to ALTERNATE DUTY BACKUP (ADB)
Parameter
Value
Description
Pump Control Mode
(2.7.1.4.) (Page 185) or
Pump Control Mode
(2.7.1.5.) (Page 185)
ADB Sets the control algorithm used to trip the
pump relay to ALTERNATE DUTY
BACKUP. Only one pump can run at a time.
Set the ON Setpoints
Parameter
Sample
Value
Description
ON Setpoint Pump 1
(2.7.1.6.) (Page 186)
1.3 m* Sets the level at which pump 1 turns on. The first cycle will use
this setpoint. Subsequent cycles rotate the setpoint among the
pumps.
ON Setpoint Pump 2
(2.7.1.8.) (Page 186)
1.2 m* Sets the level at which pump 2 turns on.
Set the OFF Setpoints
Parameter
Sample
Value
Description
OFF Setpoint
Pump 1 (2.7.1.7.)
(Page 186)
0.4 m** Sets the level at which pump 1 turns off. The first cycle will use
this setpoint. Subsequent cycles rotate the setpoint among the
pumps.
OFF Setpoint
Pump 2 (2.7.1.9.)
(Page 186)
0.3 m** Sets the level at which pump 2 turns off.