General Operation
7.11 Open Channel Monitoring (OCM)
SITRANS LUT400
122 Operating Instructions, 07/2019, A5E33329501-AC
3. Universal
For all other PMDs, the head-to-flow curve can be plotted based on known breakpoints,
usually supplied by the PMD manufacturer.
Vessel Type
Typical flow characterization (Page 148)
Example flumes (Page 149)
Example weirs (Page 150)
7.11.1 Method of Flow Calculation
When using the SITRANS LUT400 in a flow application, the Method of Flow Calculation
(2.15.3.1.) (Page 231) must be selected. There are two possible methods for calculating flow
with the SITRANS LUT400: absolute or ratiometric, and different information must be
entered for the device to carry out the calculation. For more details, and an example, see
Method of Flow Calculation (Page 302).
7.11.2 Common parameters
These common parameters are required for all installations.
Parameter
Sample Value
Flow
Response rate in Quick Start (Page 59)
MEDIUM
Transducer (2.1.6.) (Page 170) XRSS-5
Units (2.1.1.) (Page 168)
M
Low Calibration Point (2.2.1.) (Page 171)
1.8
High Calibration Point (2.2.2.) (Page 172)
0.4
Far Range (2.2.5.) (Page 172)
0.8