General Operation
7.10 External Totalizers and Flow Samplers
SITRANS LUT400
120 Operating Instructions, 07/2019, A5E33329501-AC
Parameter
Value
Description
Enable (2.11.3.1.) (Page 215)
Enabled
Enables External Totalizer Relay
Multiplier (2.11.3.2.) (Page 215)
4310
Click once every 4310 units
Relay Duration (2.11.3.3.)
(Page 216)
0.2 Activates the relay for 0.2 seconds
Assigned Relay (2.11.3.4.)
(Page 216)
Relay 1 Sets relay 1 to be controlled by external totalizer
Relay Logic (2.11.3.5.)
(Page 216)
Normally
Closed
Use (if necessary) to change the behaviour of the
relay assigned to the totalizer.
Default: Normally Open
Note
Ensure proper counting output
In case of running totalizers when a change is required, cycle the power to ensure proper
counting output of the relay between parameter settings.
7.10.3 Flow Sampler
Use the External Sampler (2.11.4.) (Page 216) function to activate the flow sampler relay
based on volume and time.
Counter Formula
1 contact every x units, where x = value set
in Multiplier (2.11.4.2.) (Page 217)
Multiplier (2.11.4.2.) (Page 217) is preset to 1 so the
default number of contacts for a pumped volume cycle
is one contact per unit of volume.
Example: To click once every 4310 units, set Multiplier (2.11.4.2.) (Page 217) to 4310.
The totalizer source, and units depend on the volume configuration:
Volume Configuration
Totalizer Source
Units Source
Vessel Shape (2.6.1.) (Page 180) =
NONE
Totalizers (2.16.)
(Page 237)
Flowrate Units (2.15.3.7.)
(Page 233)
Vessel Shape (2.6.1.) (Page 180) =
any setting other than NONE
Totalizers (2.7.3.)
(Page 194)
Volume Units (2.6.2.) (Page 181)
By using Multiplier (2.11.4.2.) (Page 217), the relay contacts can be based on a volume
other than a multiple of ten.
Parameter
Value
Description
Enable (2.11.4.1.) (Page 216)
Enabled
Enables Flow Sampler Relay
Multiplier (2.11.4.2.) (Page 217)
4310
Click once every 4310 units
Interval (2.11.4.3.) (Page 217) 2 Sets the INTERVAL (in hours) of the relay con-
tact, usually long.
Relay Duration (2.11.4.4.)
(Page 217)
0.2 Sets the DURATION (in seconds) of the relay
contact, usually short.