EasyManua.ls Logo

Siemens SITRANS LUT400 - Common Wiring Problems; Reducing Electrical Noise; Reducing Acoustical Noise

Siemens SITRANS LUT400
330 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SITRANS LUT400
278 Operating Instructions, 07/2019, A5E33329501-AC
Try moving the electronics to a different location. Often moving the electronics a few meters
farther from the source of noise will fix the problem. Shielding the electronics is also an
option, but it should be a last resort. Proper shielding is expensive and is difficult to install
properlythe shielding box must enclose the SITRANS LUT400 electronics completely, and
all wires must be brought to the box through grounded metal conduit.
11.5.3 Common Wiring Problems
Make sure that the transducer shield wire is connected at the electronics end only. Do not
ground it at any other location.
Do not connect the transducer shield wire to the white wire.
The exposed transducer shield wire must be as short as possible.
Connections between the wire supplied with the transducer, and any customer installed
extension wire should only be grounded at the LUT400.
On Siemens transducers the white wire is negative and the black wire is positive. If the
extension wire is colored differently, make sure that it is wired consistently.
Extension wire must be shielded twisted pair. See the installation section for specifications.
11.5.4 Reducing Electrical Noise
Ensure that the transducer cable does not run parallel to other cables carrying high
voltage or current.
Move the transducer cable away from noise generators like variable speed drives.
Put the transducer cable in grounded metal conduit.
Filter the noise source.
Check grounding.
11.5.5 Reducing Acoustical Noise
Move the transducer away from the noise source.
Use a stilling well.
Install a rubber or foam bushing or gasket between the transducer and the mounting
surface.
Relocate or insulate the noise source.
Change the frequency of the noise. Ultrasonic devices are sensitive to noise in the
frequency range of the transducer employed.
Check that transducer is not mounted too tightly; only hand-tight.

Table of Contents

Other manuals for Siemens SITRANS LUT400

Related product manuals