SITRANS LUT400
198 Operating Instructions, 07/2019, A5E33329501-AC
Low Level Value OFF (2.8.2.3.)
Sets the material level (defined in Units (2.1.1.) (Page 168)) at which the Low Level Alarm
will de-activate.
Values
Range: 0.000 to 99999.000
Default: 0.000
Assigned Relay (2.8.2.4.)
Determines which relay (if any) will be activated when the Low Level Alarm activates.
Options
*
NO RELAY
RELAY 1
RELAY 2
RELAY 3
Alarm State (2.8.2.5.)
Read only. Used to view the current state of the Low Level Alarm.
Options
ACTIVE
INACTIVE
9.2.8.3 Switch (Discrete Input) Alarm (2.8.3.)
Reported when Discrete Input (Discrete Input Number (2.8.3.2.) (Page 198)) is in a
predefined state (Discrete Input State (2.8.3.3.) (Page 199)).
Enable (2.8.3.1.)
Enables/disables Switch Alarm.
Options
ENABLED
*
DISABLED
Discrete Input Number (2.8.3.2.)
Determines which discrete input to monitor for Switch Alarm.
Options
*
DISCRETE INPUT 1
DISCRETE INPUT 2