General Operation
7.11 Open Channel Monitoring (OCM)
SITRANS LUT400
128 Operating Instructions, 07/2019, A5E33329501-AC
Application information
Designed to be installed directly into pipelines and manholes
Leopold Lagco may be classed as a rectangular Palmer-Bowlus flume
Sized by pipe (sewer) diameter
For rated flows under free flow conditions, the head is measured at a point upstream
referenced to the beginning of the converging section. Refer to the following table:
Flume Size
(pipe diameter in inches)
Point of Measurement
cm
inches
4-12
2.5
1
15
3.2
1.25
18 4.4 1.75
21
5.1
2
24 6.4 2.5
30
7.6
3
42
8.9
3.5
48
10.2
4
54
11.4
4.5
60
12.7
5
66
14.0
5.5
72
15.2
6
7.11.4.5 Cut Throat Flume
Plan View
Application Information
Similar to Parshall flume except that the floor is flat bottomed and throat has no virtual
length.
Refer to manufacturer’s specifications for flow equation and point of head measurement.