SITRANS LUT400
268 Operating Instructions, 07/2019, A5E33329501-AC
11.2 Device Status Icons
LUI Icon
PDM Icon
Priority Level
1
Meaning
1
Maintenance alarm
Measurement values are not valid
2
Maintenance warning: maintenance demanded
immediately
Measured signal still valid
3
Maintenance required
Measured signal still valid
1
Process value has reached an alarm limit
2
Process value has reached a warning limit
3
Process value has reached a tolerance limit
1
Configuration error
Device will not work because one or more pa-
rameters/components is incorrectly configured
2
Configuration warning
Device can work but one or more parame-
ters/components is incorrectly configured
3
Configuration changed
Device parameterization not consistent with pa-
rameterization in project. Look for info text.
1
Manual operation (local override)
Communication is good; device is in manual
mode.
2
Simulation or substitute value
Communication is good; device is in simulation
mode or works with substitute values.
3
Out of operation
Communication is good; device is out of action.
Data exchanged
No data exchange