General Operation
7.7 Pump Control
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
105
7.7.2.1 Set the common parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the device, set your test values to be the same as the
sample values.
Sensor Mode (2.1.2.) (Page 168)
Response Rate in Quick Start (Page 59)
Transducer (2.1.6.) (Page 170)
Units (2.1.1.) (Page 168) M
Low Calibration Point (2.2.1.) (Page 171)
High Calibration Point (2.2.2.) (Page 172)
7.7.2.2 Set Relays to ALTERNATE DUTY ASSIST (ADA)
Pump Control Mode (2.7.1.4.)
(Page 185) or Pump Control Mode
ADA Sets the control algorithm used to trip the pump
relay to ALTERNATE DUTY ASSIST. Multiple
pumps can run simultaneously.
7.7.2.3 Set the ON Setpoints
ON Setpoint Pump 1
(2.7.1.6.) (Page 186)
1.0 m* Sets the level at which pump 1 turns on. The first
cycle will use this setpoint. Subsequent cycles
rotate the setpoint among the pumps. For exam-
ple: In cycle 1, pump 1 turns on at 1 m. In the
next cycle, pump 2 will turn on at 1 m.
ON Setpoint Pump 2
1.1 m* Sets the level at which pump 2 turns on.
1)
Sample values denoted by asterisks in illustration on Setting a pump down (wet well) group
(Page 104).