171
When
is set to NO TRANSDUCER, the LOE fault will display
immediately.
An Echo Profile (3.2.1.) (Page 241) cannot be requested from LUI when
is set to NO TRANSDUCER. The local push button will not operate.
9.2.1.7 Frequency (2.1.7.)
Adjust the shot transmit pulse frequency (in kHz).
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
9.2.1.8 Long Shot Duration (2.1.8.)
Adjust the duration of the long shot transmit pulse (in µs).
Range: 100.000 to 2000.000
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
9.2.1.9 Short Shot Duration (2.1.9.)
Adjust the duration of the short shot transmit pulse (in µs).
Range: 100.000 to 2000.000
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
9.2.2 Calibration (2.2.)
9.2.2.1 Low Calibration Point (2.2.1.)
Distance from sensor reference point
1
to Low Calibration Point defined in Units (2.1.1.)
(Page 168).
1)
The point from which level measurement is referenced (see Sensor Mode (2.1.2.)
(Page 168) for illustration).