Commissioning
6.3 Quick Start Wizards
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
67
Maximum Volume
The maximum volume of the vessel. Enter the vessel volume corresponding to the High
Calibration Point. For example, if your maximum vessel volume is 8000 L, enter a value of
8000.
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
BACK, CANCEL, FINISH
(Display returns to 1.1 Quick Start menu when Quick Start is successfully completed or
cancelled. If CANCEL is selected, no changes are written to the device.)
To transfer Quick Start values to the device and return to Program menu, press DOWN
arrow
(Finish). Then press LEFT arrow three times to return to Measurement mode.
6.3.1.3 QS Flow
Use this wizard to configure simple flow applications.
(Visible on LUT430 (Pump and Flow), and LUT440 (OCM) configured models only.
1. Press RIGHT arrow to activate PROGRAM mode and open menu level 1: MAIN
MENU.
2. Press RIGHT arrow
two times to navigate to menu item 1.1.1.
3. Press RIGHT arrow
to open QS Flow.
4. At each step, press DOWN arrow
to accept default values and move directly to the
next item, or RIGHT arrow
to open Edit mode: the current selection is highlighted.