SITRANS LUT400
272 Operating Instructions, 07/2019, A5E33329501-AC
46
46
* The TS-3 temperature sensor
failed.
Inspect attached cabling and any
termination points to ensure no
disconnection or damage; repair/
replace if necessary. If no issue
with cabling, contact your local
47
47
Poor signal from the application.
Poor installation or high noise
level.
Verify installation.
121
121
Flow calculations are not config-
ured properly. Incorrect parame-
ter settings.
Reconfigure the unit. Check the
configuration. If fault persists, do
a master reset.
122
122
Flow calculations encountered an
error.
Reconfigure the unit. Check the
breakpoints. If fault persists, do a
master reset.
123
123
Flow log could not restore the
settings.
Reconfigure the unit. Check the
flow log settings. If fault persists,
do a master reset.
124
124
Flow log is not configured proper-
ly.
Reconfigure the unit. Check the
flow log settings. If fault persists,
do a master reset.
125
125
Flow log error.
Log failed.
Verify that the drive where the log
file resides is not full. Copy the
log file to a computer and delete
it from the device.
126
126
Failed to open log file. Verify that the drive where the log
file resides is not full. Copy the
log file to a computer and delete
it from the device.
127
127
Failed to close log file. Verify that the drive where the log
file resides is not full. Copy the
log file to a computer and delete
it from the device.
128
128
Log file read error.
Error reading file. Unexpected
error.
Verify that the drive where the log
file resides is not full. Copy the
log file to a computer and delete
it from the device.
130
130
Configuration error.
One or more settings invalid.
Adjust/correct relay assignments
or setpoints.