Connecting
5.1 Connecting SITRANS LUT400
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
37
AC: 100-230 V AC 15%, 50/60 Hz, 36 VA (10W) DC: 10-32 V DC, 10W
e device is connected to a reliable ground.
1. To wire for power, strip the cable jacket for approximately 70 mm (2.75") from the end of
the cable, and thread the wires through the gland
1
2. Connect the wires to the terminals as shown: the polarity is identified below the terminal
block.
3. Ground the device according to local regulations.
1)
If cable is routed through conduit, use only approved suitable-size hubs for waterproof
applications.
Note
For AC power connections:
• The equipment must be protected by a 15 A fuse, or circuit breaker on all current
-carrying
conductors in the building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect switch,
must be in close proximity t
o the equipment and within easy reach of the operator, and must
-carrying conductors.