Commissioning
6.3 Quick Start Wizards
SITRANS LUT400
64 Operating Instructions, 07/2019, A5E33329501-AC
Start of QS Volume Wizard
Note
The introduction screen is displayed only on the device when using the local push
buttons.
This screen is not part of the Quick Start when using SIMATIC PDM.
Shows the type of Wizard to be executed.
Options
CANCEL, START
Transducer
Specifies the Siemens transducer connected to the device.
Options NO TRANSDUCER, XRS-5, XPS-10, XPS-15, XCT-8, XCT-12, XPS-30, XPS-40,
XLT-30, XLT-60, STH
Default: NO TRANSDUCER
Temperature Source
Source of the temperature reading used to adjust the speed of sound.
Options
TRANSDUCER, FIXED TEMPERATURE, EXTERNAL TS-3, AVERAGE OF SENSORS
Default: TRANSDUCER
See Temperature Source (2.12.1.3.) (Page 218) Temperature Source for more details.
Fixed Temperature
Use this feature if a temperature sensing device is not used.
Value
Range: -100.0 to +150.0 °C
Default: +20.0 °C
This parameter is only displayed if FIXED TEMPERATURE selected for Temperature
Source.