Commissioning
6.3 Quick Start Wizards
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
73
Maximum Head
The maximum level value associated with the PMD.
Value
Range: 0.000 to 60.000
Default: 60.000
Zero Head Offset
The difference (positive or negative) between Low Calibration Point and zero head (level at
zero flow).
Value
Range: -60.000 to 60.000
Default: 0.000
Flowrate Units
The volume units used to display total flow.
Options
L/S, L/MIN, CUFT/S, CUFT/D, GAL/MIN, GAL/D, IMPGAL/MIN, IMPGAL/D, CUM/H,
CUM/D, MMGAL/D, USER DEFINED *
Default: L/S
* If USER DEFINED option selected, the value must be set after completing the wizard. See
User Defined Unit (2.15.3.8.) (Page 234).
Maximum Flow at 20 mA
The maximum flowrate.
Value
Range: -999 to 9999999
Default: 100
Flowrate Decimal
The maximum number of decimal units to be displayed.
Options
NO DIGITS, 1 DIGIT, 2 DIGITS, 3 DIGITS
Default: NO DIGITS
Low Flow Cutoff
Eliminates totalizer activity for head levels at or below the cutoff value.
Value
Range: 0.000 to 60.000
Default: 0.000