7-8
The panel, battery-backed, unregulated dc bulk power is available from the SPS via the
NAC and the 24V Aux power terminals (1 pair only, ref fig 7-4). NACs not configured
as switched outputs may be configured as auxiliary power point type in the 4100
Programmer. All of these are power-limited.
Review the following guidelines before using the SPS for auxiliary power.
Voltage rating: 24 VDC (nominal), 2 V P-P ripple (maximum).
The total auxiliary current available for non-alarm is 5 A. The total current available
for the entire SPS is 9 A, including NAC, auxiliary, and card power.
All wiring is 0.75 mm
2
to 4 mm
2
.
All SPS powered field wiring requires a ferrite bead (ref fig 7.1).
All wiring that leaves the building requires overvoltage protection. Install
module
2081-9044 wherever wire enters or exits the building. A maximum of four 2081-
9044 Modules may be connected to one channel.
When a NAC is configured as an auxiliary power circuit, no end-of-line resistor
is used.
External wiring is not supervised unless an end-of-line relay is wired, coil to
auxiliary power, and Normally Open contacts are monitored by a system power
point. Relay current must be considered as part of the load.
Programming is required for the dedicated Auxiliary Power output (TB3).
The following devices may be connected to the 2 A Auxiliary Power:
- 2088-series relays and door holders
- 2098-series four-wire smoke detectors
- 2190-series monitor and signal ZAMs
- 4090-series IDNet ZAMs
- 4098-series four-wire smoke detectors and duct detectors
- 2190-9039 Printer
- 4190-9050/9051 4-20 mA ZAMs
- 4603-9101 LCD Annunciator
The Auxiliary Power output is rated at 2 A dc.
Where multiple loads are to be connected with individual protection, a Fused DC
Distribution board may be fitted directly to the SPS bracket adjacent to TB3.
Continued on next page
SPS Auxiliary Power Wiring
Overview
Guidelines

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals