8-9
To connect the IDNet card to appliances using Class B wiring, read the following
instructions.
1. On TB1, jumper IDNetB+ to IDNet A+, and jumper IDNetB- to IDNetA-. If the
jumper is absent, a Class A Trouble will be indicated on LED 2.
2. Route wire between 0.75 mm
2
and 4 mm
2
from the IDNetA+, IDNetA-, (or B+,
B-) outputs on TB1 of the IDNet card to a junction box. Begin “T” tapping at the
junction box.
3. Up to 40 devices maximum.
4. Sounder bases or 6 Point I/O modules in separate zones may not be wired in
Class B.
The illustration below shows Class B wiring.
+
1
2
1 21212
Figure 8-6. Class B Wiring
Note: Maintain correct polarity on terminal connections. Do not loop wires
under terminals.
Wiring to IDNet Devices, Continued
Class B Wiring
IDNET CARD
IDNET DEVICES
0.75 mm
2
and 4 mm
2
FERRITE BEAD (see fig 7.1)

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485

Related product manuals