9-2
The 4100U can connect to PCs running important utilities, such as diagnostics,
programming, CPU firmware downloading, and channel monitoring. It connects to PCs
running all of these utilities via the service port on the CPU daughter card. When a PC is
located remotely from the FACP, the 4100-9832 Service Modem is used.
There are three basic software modes that the service port or service modem can be used
to connect to:
Service and Diagnostics Mode
Data Transfer Interface Mode
Master Bootloader Interface Mode
Each mode is described below.
Service and Diagnostics Mode. The default functionality when a PC is connected to the
FACP. On a PC, this mode provides application startup messages, an ASCII interface to a
UI command set for diagnostics, and event reporting. The PC must be running terminal
emulation software (e.g., Hyperterm). Connection to a PC is made via serial port or
service modem.
Important: When connecting via the service port, ensure your Flow Control
is set to NONE in the Port Settings of your terminal emulator.
Laptop/PC running
terminal emulation software
4100 Panel (with CPU modem card)
running application
serial download
cable
Modem
Laptop/PC running
terminal emulation software
Option 1 Option 2
Figure 9-1. Service and Diagnostic Interface
Data Transfer Interface Mode. In this mode, the 4100 Programmer is enabled. This
allows for slave downloading, as well as downloading a configuration and audio
messages to the FACP, and uploading a configuration or history log from the FACP.
Connection to a PC is made via serial port or service modem.
Laptop/PC running
Programmer software
4100 Panel (with CPU modem card)
running application
serial download
cable
Modem
Laptop/PC running
Programmer software
Option 1 Option 2
Figure 9-2. Data Transfer Interface
Note: The standard Simplex modem is not currently approved for use in Australia.
Continued on next page
Software Modes
Overview
Software Modes

Table of Contents

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485