LC700 – User’s Guide
3.84
It is necessary a source to feed the relay. The user can use the PS-AC-R or an external source.
One source may load several groups since its capacity is enough. Just one group per phase, but the
groups may have different phases.
Technical Specifications
ARCHITECTURE
Number of outputs 16
Number of groups 2
Number of points per group 8
ISOLATION
The driver for each relays is optically Isolated
from IMB up to
5000 Vac
Each group of 8 relays has one common contact.
EXTERNAL SOURCE
Voltage source for each group 20 - 30 Vdc
Maximum current per group 90 mA @ 24 Vdc
Maximum consumption per point 11.3 mA @ 24 Vdc
Power Supply Indicator per group Green LED
INTERNAL SOURCE
Provided by the IMB bus 5 Vdc @ 30 mA maximum
Total Maximum Dissipation 0.15 W
Power Supply Indicator None
OUTPUTS
Vac Range
20-250 Vac
Vdc Range
20-110 Vdc
Maximum Current for 250 Vac
5 A (resistive); 2 A (inductive)
Maximum Current for 30 Vdc
5 A (resistive); 2 A (inductive)
Maximum total current per group 10 A
Initial contact resistance maximum 100 mΩ
Status display Yellow LED
Indicator Logic LED ON - relay coil is active
Leakage Current
M-123:0
M-127:500μA @ 100Vac
Over load protection per output Should be provided externally
SWITCHING INFORMATION
Operate Time 10 ms maximum
Release Time 10 ms maximum
ELECTRICAL SERVICE LIFE
Switching Cycles
20.000.000 minimum operations @ maximum
current
DIMENSIONS AND WEIGHT
Dimensions (W x D x H)
39.9 x 137.0 x 141.5 mm;
(1.57 x 5.39 x 5.57 in)
Weight 0.301 kg
CABLES
One Wire 14 AWG (2 mm
2
)
Two Wires 20 AWG (0.5 mm
2
)