Modules And Accessories
3.95
MB-700 –Modbus RTU TCP/IP Processor Module
Part Number
MB-700 (Modbus RTU/TCP Processor Module)
Description
The MB-700 is a multi-function module integrated into the SYSTEM302 that has two types of
functions: bypass (gateway MODBUS TCP/IP e MODBUS RTU) and Modbus data concentrator.
The MB-700 allows the remote configuration of devices that use the MODBUS RTU protocol. So,
when the device receives a Modbus TCP/IP message and does not have its address, it will pass the
communication frame to a lower level of the Modbus RTU network. At the same time the MB-700
collects data from lower levels of this network communicating with the CPU through the Ethernet
network. It uses a PS-AC-R Power Source Module. Please refer to the MB-700 manual for further
details.
MB70
0
-M
o
d
bus
Pr
o
c
es
s
or
1B
2B
3B
4B
5B
6B
7B
Fct Init / Reset
ETH
10Mbps
Fail
232
/RTS
Tx
NC
Rx
GND
/CTS
1
3
2
4
5
6
T/R+
+
SYNC
-
T/R-
485
NC
GND
8B
9B
10B
Figure 3.62 – Modbus RTU-TCP/IP Processor MB-700
Technical Specifications
CONTROLLER
Type 32 Bit RISC (CPU Clock @ 25 MHz)
Performance 50 MIPS
Code memory
2 Mbytes, 32 Bits Flash Memory (recordable
Firmware)
Data memory
2 Mbytes, 32 Bits NVRAM (Data storage and
configuration)
COMMUNICATION PORTS
Ethernet 1 Port Ethernet @ 10 Mbits (Connector RJ-45)
Serial
1 Port EIA 232 @ 9.6Kbps-115,2 Kbps
(Connector RJ11)
1 Port EIA 485 @ 9.6 Kbps-115.2 Kbps
Synchronism Channel
1 Port Independent com DMA-Baud rate 31.25
Kbps (SYNC)