Connecting accessories
Note!
Inepro meter
Inepro meters are automatically given the mod bus address 234 by Solar-Log™ during
the detection process.
This address is therefore not allowed to be used for other devices.
After the configuration, the display on the Inepro meter alternates between the meter
status and the address display (ID=EA). This can be used to check if Solar-Log™ has cor-
rectly detected the meter.
All RS485 meters have to be terminated with an 120Ω resistor between the two pins
used.