097-93100-01 Revision C – February, 2010 TimeCreator 1000 User’s Guide 135
Appendix A Alarms, Events and SNMP Traps
Alarm Messages
12 IMCFAIL Critical IMC operational
failure
Indicates that
the specified
IMC module is
not functioning
properly
Re-seat the IMC
module, if issue
not is resolved,
replace module
IMC recovered
from operational
failure
Indicates that
the specified
IMC module is
now functioning
properly
No action required
13 IMCNCOMP Minor IMC and IOC <#>
incompatible
Indicates that
the IMC and IOC
modules are not
compatible
Need to upgrade
IOCs or IMC to
same firmware
versions
IMC and IOC <#>
compatible
IMC and IOC
modules are
compatible
No action required
14 GPSNCOM Minor GPS antenna
communication
failed
Indicates that
the GPS signal
is not connected
Check antenna
cable, lightning
arrestor and
antenna; replace
faulty item
GPS antenna
communication
restored
Indicates that
the GPS signal
is OK
No action required
15 MTIETEXC Minor Port <#> has
exceeded the
MTIE-t threshold,
<value>
Indicates that
the MTIE-t error
rate has
exceeded the
user-set
threshold
Check cable and
NE (network
element) on that
port
Port <#> is within
the MTIE-t
threshold,
<value>
Indicates that
the MTIE-t error
rate is within the
user-set
threshold
No action required
Table A-2. System Notification Messages - Alarms (Continued)
Index
Trap Name
(trapID)
Severity
(default)
Trap Messages
(trapDescription)
Description
Corrective